8-Channel circuit breaker
PC-0824-480-0
Characteristics
Benefits
› Adjustable tripping current for each output channel via current selector switch
› Selective immediate switch off of defective circuits in the event of critical supply voltage
› Sequential and load-dependent switching-on of channels
› Comprehensive single-channel-diagnostics and remote switching on/off of each output channel via 2-wire-interface
› Further diagnoses of input voltage and the current of each circuit
› Group alarm contact
› 3 years warranty
Product | 8-Channel circuit breaker |
Order number | PC-0824-480-0 |
Series | BASIC SMART |
Input
Rated input voltage | 24 Vdc |
Input voltage range | 18 Vdc to 30 Vdc |
Max. continuous current of the module | 48 A |
Max. continuous current feed terminal (+) | 40 A |
Überspannungsschutz | Suppressordioden |
Max. ripple of the feeding input voltage | 3 % |
Switch-on threshold | 20.00 V |
Output
Rated output voltage | 24 Vdc |
Rated Output Current | 6 A |
Rated Output Current Adjustable | 0.5,1,2,3,4,6 |
Rated Output Current per Output Channel | 6 A |
Output voltage range | 24 Vdc |
Number of Output Channels | 8 |
Switch-off threshold | 18 V |
Max. voltage drop between input and output | 155 mV |
Max. power loss | 8.,6 W @ 8 x 6 A |
Max. waiting time after switching off an output after an overload (thermal relaxation) | 20 s |
Idle current @ 24 V | 48 mA |
Max. feedback resistance | 35 Vdc |
Power losses in stand-by mode | 1.15 W |
Parallel connection of outputs | Not allowed |
Series connection of outputs | Not allowed |
Release Characteristics | Active current limiting |
Signaling
Signal output S2 | 24 Vdc, max. 25 mA (status output channels) |
Signal output S3 | 24 Vdc, max. 25 mA (Common signalling output) |
Status display | Green, yellow, red LED |
Environment
Climate class according to EN 60721 | 3K3 |
Ambient temperature | -25 °C to 70 °C / -13 °F to 158 °F |
Storage temperature | -25 °C to 85 °C / -13 °F to 185 °F |
Humidity without condensation | 5 % to 96 % |
Cooling type | natural convection |
Required minimum distance (side) | 0 mm |
Required minimum distance (top/bottom) | 40 mm |
Protection and Safety
Degree of pollution | 2 |
Protection class according to EN 61140 | III, without PE connection |
Safety extra low voltage (SELV/PELV) | IEC 60364-4-41 (DIN VDE 0100-410) |
Size and Weight
Width | 42 mm / 1.65 in |
Height | 127 mm / 5 in |
Depth | 116.5 mm / 4.59 in |
Depth incl. DIN TH35 | 124 mm / 4.88 in |
Weight | 0.49 kg / 1.08 lbs |