Isolating transformer
TIM 60
Characteristics
General data
The isolating transformers of the TIM series ensure safe galvanic isolation of the primary circuit from the secondary circuit. The transformers are manufactured according to EN (IEC) 61558-2-4 and have a protection class of IP 20.
Benefits
› Integrated short-circuit and overload protection
› Dual output coils for series or parallel connection
› Excellent moisture protection and low noise emission thanks to XtraDenseFill resin encapsulation
› Screw terminal connections under cover with strain relief
Product | Isolating transformer |
Order number | TIM 60 |
Series | TIM |
Power | 60 VA |
Input | 230 V |
Output | 2 x 115 V • 0.26 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 9 W |
No-Load Losses | 3.1 W |
Short circuit voltage uk | 13.9 % |
EN Insulation class | A (105°C) |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 83.2 % |
General
Short circuit proof | conditionally short-circuit proof |
Switching group | Ii |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 20 |
Protection class (prepared) | II |
Overvoltage category | III |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Size and Weight
Width | 77 mm / 3.03 in |
Height | 90 mm / 3.54 in |
Depth | 166 mm / 6.54 in |
Weight | 1.52 kg / 3.351 lbs |
Low Voltage Directive | EN 61558-2-4 |
VDE Approval |