Control- and isolating transformer
STU 63/2x115
Characteristics
General data
The control transformers of the STU series are designed for universal voltage adjustment and safe galvanic isolation of the primary circuit from the secondary circuit. The unique BLOCK IMPEX vacuum impregnation process provides excellent protection against external influences while reducing noise levels. The robust metal base plate with elongated holes ensures easy and secure mounting.
Benefits
› Control and isolating transformer according to EN (IEC) 61558-2-2 and EN (IEC) 61558-2-4
› Very good inrush behavior due to reduced inrush currents
› High power density through a compact design concept
› Touch-protected connection terminals according to UVV BGV A3
Product | Control- and isolating transformer |
Order number | STU 63/2x115 |
Series | STU |
Power | 63 VA |
Input | 230 V / 400 V / 460 V / 520 V ± 20 V |
Output | 2 x 115 V • 0.27 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Term Power / instantaneous output | 110 VA |
EN Insulation class | B (130°C) |
UL Insulation class | class 105 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 84 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Ii |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Flat plug connection |
Size and Weight
Width | 84 mm / 3.31 in |
Height | 94 mm / 3.7 in |
Depth | 76 mm / 2.99 in |
Weight | 1.5 kg / 3.307 lbs |
Low Voltage Directive |
EN 61558-2-2 EN 61558-2-4 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |
VDE Approval |
VDE 0570-2-x (DIN EN 61558-2-x) |