2-Channel circuit breaker

PM-0824-120-0

Characteristics

Benefits

 Adjustable tripping current for each output channel via current selector switch

 Selective immediate switch off of defective circuits in the event of critical supply voltage

 Sequential and load-dependent switching-on of channels

 Comprehensive single-channel-diagnostics and remote switching on/off of each output channel via 2-wire-interface

 Further diagnoses of input voltage and the current of each circuit

 Group alarm contact

 3 years warranty

Product Search
Product 2-Channel circuit breaker
Order number PM-0824-120-0
Input
Rated input voltage 24 Vdc
Input voltage range 18 Vdc to 30 Vdc
Max. continuous current of the module 12 A
Max. continuous current feed terminal (+) 40 A
Überspannungsschutz Suppressordioden
Max. ripple of the feeding input voltage 3 %
Switch-on threshold 19.50 V
Output
Rated output voltage 24 Vdc
Rated Output Current 6 A
Rated Output Current Adjustable 0.5,1,2,3,4,6
Rated Output Current per Output Channel 6 A
Output voltage range 24 Vdc
Number of Output Channels 2
Switch-off threshold 18 V
Max. voltage drop between input and output 155 mV
Max. power loss 2.5 W @ 2 x 6 A
Max. waiting time after switching off an output after an overload (thermal relaxation) 20 s
Idle current @ 24 V 32 mA
Max. feedback resistance 35 Vdc
Power losses in stand-by mode 0.77 W
Parallel connection of outputs Not allowed
Series connection of outputs Not allowed
Release Characteristics Active current limiting
Signaling
Signal output S2 24 Vdc, max. 25 mA (status output channels)
Signal output S3 24 Vdc, max. 25 mA (Common signalling output)
Status display Green, yellow, red LED
Environment
Climate class according to EN 60721 3K3
Ambient temperature -25 °C to 70 °C / -13 °F to 158 °F
Storage Temperature -25 °C to 85 °C / -13 °F to 185 °F
Humidity without condensation 5 % to 96 %
Cooling type natural convection
Required minimum distance (side) 0 mm
Required minimum distance (top/bottom) 40 mm
Protection and Safety
Degree of pollution 2
Protection class according to EN 61140 III, without PE connection
Safety extra low voltage (SELV/PELV) IEC 60364-4-41 (DIN VDE 0100-410)
Size and Weight
Width 42 mm / 1.65 in
Height 127 mm / 5 in
Depth 116.5 mm / 4.59 in
Depth incl. DIN TH35 97 mm / 3.82 in
Weight 0.2 kg / 0.44 lbs

This could also be of interest to you

PCC-0124-100-2
Single-phase, primary switched mode power supply
Product details
PC-0524-400-0
Charge- and control unit
Product details
PC-0724-800-0
Electronic circuit breaker with thermomagnetic characteristic
Product details
PM-0824-240-0
Electronic circuit breaker with current limiting
Product details
PM-9824-152-0
Electronic circuit breaker with current limiting and non-adjustable tripping currents
Product details