Control- and isolating transformer

UTT1-4-23

Characteristics

General data

The control transformers of the UTT1 series feature a universal input voltage range and ensure safe galvanic isolation of the primary circuit from the secondary circuit. The multifunctional base brackets provide variable mounting options, and the upright design reduces space requirements. The integrated crane eyelets facilitate transport and installation.

Benefits

 Control and isolating transformer according to EN (IEC) 61558-2-2 and EN (IEC) 61558-2-4

 Patented mounting technology

 Primary side ±5% taps for voltage adjustment

 Excellent corrosion protection and low noise emission thanks to BLOCK IMPEX vacuum impregnation

 Fixed, touch-protected screw terminals according to UVV BGV A3

Product Control- and isolating transformer
Order number UTT1-4-23
Series TT1
Power 4,000 VA
Input 208 V / 230 V / 380 V / 400 V / 415 V / 440 V / 460 V / 480 V / 500 V / 525 V / 550 V / 575 V / 600 V
Output 115 V • 17.4 Aac
or 230 V • 17.4 Aac
Phases 1
Frequency range 50 Hz to 60 Hz
Short-Circuit Losses 161 W
No-Load Losses 68 W
Short-Term Power / instantaneous output 11,000 VA
EN Insulation class F (155°C)
UL Insulation class class 155
Duty Cycle 100 %
Wire material Copper
Efficiency 94.6 %
General
Short circuit proof not short-circuit proof
Switching group IIi
Cooling type AN
Environment
Ambient temperature -20 °C to 40 °C / -4 °F to 104 °F
Max. installation height 2,000 m / 6,562 ft
Protection and Safety
Protection type IP 00
Protection class (prepared) I
Overvoltage category III
Degree of contamination 1
Electrical Connections
Input terminal Screw terminal
Output terminal Screw terminal
Terminal PE Screw terminal
Size and Weight
Width 240 mm / 9.45 in
Height 335 mm / 13.19 in
Depth 185 mm / 7.28 in
Weight 36 kg / 79.366 lbs
Low Voltage Directive EN 61558-2-2
EN 61558-2-4
RoHS compliant EN IEC 63000
Approval cURus - Recognized UL 5085-1/-2; CSA 22.2

Premier Farnell Limited

Product link

This could also be of interest to you

UTT1-3,2-23
Control- and isolating transformer • 1ph • 3200 VA • IN: 208-600 Vac • OUT: 2 x 115 Vac
Product details
UTT1-6-23
Control- and isolating transformer • 1ph • 6000 VA • IN: 208-600 Vac • OUT:  115-230 Vac
Product details
TT1 4-4-23
Control- and isolating transformer • 1ph • 4000 VA • IN: 380-420 Vac • OUT: 2 x 115 Vac
Product details
TT1 4-44-23
Control- and isolating transformer • 1ph • 4000 VA • IN: 418-462 Vac • OUT: 2 x 115 Vac
Product details
TT1 4-5-23
Control- and isolating transformer • 1ph • 4000 VA • IN: 475-525 Vac • OUT: 2 x 115 Vac
Product details
TT1 5-4-23
Control- and isolating transformer • 1ph • 5000 VA • IN: 380-420 Vac • OUT: 2 x 115 Vac
Product details