Control- and isolating transformer
UTT1-3,2-23
Characteristics
General data
The control transformers of the UTT1 series feature a universal input voltage range and ensure safe galvanic isolation of the primary circuit from the secondary circuit. The multifunctional base brackets provide variable mounting options, and the upright design reduces space requirements. The integrated crane eyelets facilitate transport and installation.
Benefits
› Control and isolating transformer according to EN (IEC) 61558-2-2 and EN (IEC) 61558-2-4
› Patented mounting technology
› Primary side ±5% taps for voltage adjustment
› Excellent corrosion protection and low noise emission thanks to BLOCK IMPEX vacuum impregnation
› Fixed, touch-protected screw terminals according to UVV BGV A3
Product | Control- and isolating transformer |
Order number | UTT1-3,2-23 |
Series | TT1 |
Power | 3,200 VA |
Input | 208 V / 230 V / 380 V / 400 V / 415 V / 440 V / 460 V / 480 V / 500 V / 525 V / 550 V / 575 V / 600 V |
Output | 2 x 115 V • 13.9 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 169 W |
No-Load Losses | 49 W |
Short-Term Power / instantaneous output | 8,970 VA |
EN Insulation class | F (155°C) |
UL Insulation class | class 155 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 93.6 % |
General
Short circuit proof | not short-circuit proof |
Switching group | II |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 1 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Screw terminal |
Size and Weight
Weight | 24.2 kg / 53.352 lbs |
Low Voltage Directive |
EN 61558-2-2 EN 61558-2-4 |
RoHS compliant | EN IEC 63000 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |