Control- and safety isolating transformer
STSU 500/24 - Discontinued types - not for new designs
Characteristics
Benefits
› Dual input voltage 230 and 400 Vac
› Quick to cable up thanks to the use of screw terminals
› Very good switch-on behaviour thanks to reduced starting currents
› Up to 250 VA with combination footplate for bolted and rail mounting
› Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation
› Contact protected screw connection terminals complying with UVV BGV A3
› Simple mounting due to robust metal footplate with oval slots
› 63 - 250 VA with combination footplate for bolted and rail mounting
› Primary side ±15 V tappings for voltage adjustment
Product | Control- and safety isolating transformer |
Order number | STSU 500/24 |
Series | STSU |
Power | 500 VA |
Input | 230 V / 400 V ± 15 V |
Output | 2 x 12 V • 20.8 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 29 W |
No-Load Losses | 15 W |
Short-Term Power / instantaneous output | 2,000 VA |
Short circuit voltage uk | 5.3 % |
EN Insulation class | B (130°C) |
UL Insulation class | class 130 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 91.9 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Iii0 |
Shield winding | Yes |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 1 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Screw terminal |
Size and Weight
Width | 120 mm / 4.72 in |
Height | 137 mm / 5.39 in |
Depth | 124 mm / 4.88 in |
Weight | 7 kg / 15.432 lbs |
Low Voltage Directive |
EN 61558-2-2 EN 61558-2-6 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |