Control- and isolating transformer
STSU 2000/23
Characteristics
General data
The transformers of the STSU series ensure safe galvanic isolation of the primary circuit from the secondary circuit. The unique BLOCK IMPEX vacuum impregnation process provides excellent protection against external influences while reducing noise levels. The robust metal base plate with elongated holes ensures easy and secure mounting.
Benefits
› Control and isolating transformer according to EN (IEC) 61558-2-2 and EN (IEC) 61558-2-4
› Dual input voltage 230 and 400 Vac
› Very good inrush behavior due to reduced inrush currents
› Primary side ±15 V taps for voltage adjustment
› Touch-protected connection terminals according to UVV BGV A3
Product | Control- and isolating transformer |
Order number | STSU 2000/23 |
Series | STSU |
Power | 2,000 VA |
Input | 230 V / 400 V ± 15 V |
Output | 2 x 115 V • 8.7 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 47 W |
No-Load Losses | 60 W |
Short-Term Power / instantaneous output | 10,900 VA |
EN Insulation class | B (130°C) |
UL Insulation class | class 130 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 94.9 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Iii0 |
Shield winding | Yes |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 1 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Screw terminal |
Size and Weight
Width | 192 mm / 7.56 in |
Height | 185 mm / 7.28 in |
Depth | 183 mm / 7.2 in |
Weight | 26 kg / 57.32 lbs |
Low Voltage Directive |
EN 61558-2-2 EN 61558-2-4 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |