Control- and isolating transformer
ST 100/69/23
Characteristics
General data
The transformers of the ST series ensure safe galvanic isolation of the primary circuit from the secondary circuit. The unique BLOCK IMPEX vacuum impregnation process provides excellent protection against external influences while reducing noise levels. The robust metal base plate with elongated holes ensures easy and secure mounting.
Benefits
› Control and isolating transformer according to EN (IEC) 61558-2-2 and EN (IEC) 61558-2-4
› Very good inrush behavior due to reduced inrush currents
› High power density through a compact design concept
› Primary side ±5% taps for voltage adjustment
› Touch-protected connection terminals according to UVV BGV A3
Product | Control- and isolating transformer |
Order number | ST 100/69/23 |
Series | ST |
Power | 100 VA |
Input | 655 V / 690 V / 725 V |
Output | 230 V • 0.44 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 9 W |
No-Load Losses | 4 W |
Short-Term Power / instantaneous output | 225 VA |
Short circuit voltage uk | 8.2 % |
EN Insulation class | B (130°C) |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 88.5 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Ii0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 1 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Flat plug connection |
Size and Weight
Width | 84 mm / 3.31 in |
Height | 93 mm / 3.66 in |
Depth | 90 mm / 3.54 in |
Weight | 2.1 kg / 4.63 lbs |
Low Voltage Directive |
EN 61558-2-2 EN 61558-2-4 |