FAIL-SAFE transformer, control- and safety isolating transformer
FST 160/24 - Discontinued items - no longer available
Characteristics
General data
The control transformers of the FST series feature an integrated FAIL-SAFE protection device and ensure safe galvanic isolation of the primary circuit from the secondary circuit. The unique BLOCK IMPEX vacuum impregnation process provides excellent protection against external influences while reducing noise levels.
Benefits
› Control and safety isolating transformer according to EN (IEC) 61558-2-2 and EN (IEC) 61558-2-6
› High power density through a compact design concept
› Very good inrush behavior due to reduced inrush currents
› Operation possible at 50 - 60 Hz
› Primary side for input voltage 230 Vac and 400 Vac
› Mounting via integrated DIN rail mounting according to DIN 50022
Product | FAIL-SAFE transformer, control- and safety isolating transformer |
Order number | FST 160/24 |
Series | FST |
Power | 160 VA |
Input | 230 V / 400 V |
Output | 24 V • 6.67 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 14.9 W |
No-Load Losses | 5.6 W |
Short-Term Power / instantaneous output | 320 VA |
Short circuit voltage uk | 8.6 % |
EN Insulation class | B (130°C) |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 88.6 % |
General
Short circuit proof | conditionally short-circuit proof |
Switching group | Ii0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Flat plug connection |
Size and Weight
Width | 96 mm / 3.78 in |
Height | 102 mm / 4.02 in |
Depth | 102 mm / 4.02 in |
Weight | 2.9 kg / 6.393 lbs |
General
TS35 rail mounting possible | ja |
Low Voltage Directive |
EN 61558-2-2 EN 61558-2-6 |
VDE Approval |
VDE 0570-2-x (DIN EN 61558-2-x) |