Autotransformer
VT 50-EN
Characteristics
General data
The autotransformers of the VT-EN series are used for voltage adjustment without the need for galvanic isolation. The transformers feature lower weight and a smaller form factor compared to other transformer types with separate windings and can be easily mounted using robust metal base brackets with elongated holes.
Benefits
› Autotransformer according to EN (IEC) 61558-2-13
› Very high efficiency
› Excellent moisture protection and low noise emission thanks to BLOCK IMPEX vacuum impregnation
› Touch-protected connection terminals according to UVV BGV A3
Product | Autotransformer |
Order number | VT 50-EN |
Series | VT-EN |
Power | 500 VA |
Input | 110 V / 125 V / 230 V / 240 V |
Output |
110 V • 4.5 Aac oder 125 V • 4 Aac oder 230 V • 2.2 Aac oder 240 V • 2.1 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 21.2 W |
No-Load Losses | 7.3 W |
EN Insulation class | B (130°C) |
UL Insulation class | class 130 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 94.6 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Ia0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Degree of contamination | 1 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Flat plug connection |
Size and Weight
Width | 86 mm / 3.39 in |
Height | 130 mm / 5.12 in |
Depth | 120 mm / 4.72 in |
Weight | 4.5 kg / 9.921 lbs |
Low Voltage Directive | EN 61558-2-13 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |