Isolating transformer, three-phase
TT3-A500-4040-0
Characteristics
Benefits
› Safe galvanic isolation
› Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation
› Very good discharging of thermal losses by means of optimally arranged cooling channels within the coils
› Integrated crane eyes
› If desired, the transformers can be realised in individual voltages
Product | Isolating transformer, three-phase |
Order number | TT3-A500-4040-0 |
Power | 500,000 VA |
Input | 3 x 400 V |
Output | 3 x 400 V • 722 Aac |
Phases | 3 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 7111 W |
No-Load Losses | 1845 W |
Short circuit voltage uk | 3.3 % |
EN insulation class | F (155°C) |
UL Insulation class | class 180 |
Duty Cycle | 100 % |
Wire material | Aluminum |
Efficiency | 98.2 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Dyn5 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Flat copper connection |
Output terminal | Flat copper connection |
Terminal PE | Bolt connection |
Size and Weight
Width | 1075 mm / 42.32 in |
Height | 1100 mm / 43.31 in |
Depth | 630 mm / 24.8 in |
Weight | 1352 kg / 2980.65 lbs |
Low Voltage Directive | EN 61558-2-4 |
Approval cURus - Recognized | UL 1561; CSA 22.2 |