Isolating transformer, three-phase
TT3-A500-4040-0
Characteristics
General data
The isolating transformers of the TT3-A series ensure safe galvanic isolation of the primary circuits from the secondary circuits. Our unique BLOCK IMPEX vacuum impregnation process provides excellent protection against external influences while reducing noise levels. The transformers stand out with high performance ranges and low core losses.
Benefits
› Isolating transformer according to EN (IEC) 61558-2-4
› Excellent dissipation of heat losses through optimally arranged cooling channels within the windings
› Integrated crane eyelets
› Easily accessible terminals for simple installation in electrical systems
› Transformers can be customized with individual voltages upon request
Product | Isolating transformer, three-phase |
Order number | TT3-A500-4040-0 |
Series | TT3-A |
Power | 500,000 VA |
Input | 3 x 400 V |
Output | 3 x 400 V • 722 Aac |
Phases | 3 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 7111 W |
No-Load Losses | 1845 W |
Short circuit voltage uk | 3.3 % |
EN Insulation class | F (155°C) |
UL Insulation class | class 180 |
Duty Cycle | 100 % |
Wire material | Aluminum |
Efficiency | 98.2 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Dyn5 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Flat copper connection |
Output terminal | Flat copper connection |
Terminal PE | Bolt connection |
Size and Weight
Width | 1075 mm / 42.32 in |
Height | 1100 mm / 43.31 in |
Depth | 630 mm / 24.8 in |
Weight | 1352 kg / 2980.646 lbs |
Low Voltage Directive | EN 61558-2-4 |
Approval cURus - Recognized | UL 1561; CSA 22.2 |