Isolating transformer
TIM 500
Characteristics
Benefits
› Safe galvanic isolation
› Integrated short-circuit and overload protection
› Double output voltage for series or parallel connection
› Screw terminals under cover with strain relief
Product | Isolating transformer |
Order number | TIM 500 |
Power | 500 VA |
Input | 230 V |
Output | 2 x 115 V • 2.17 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 23.4 W |
No-Load Losses | 15.8 W |
Short circuit voltage uk | 4.4 % |
EN insulation class | B (130°C) |
UL Insulation class | class 130 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 92.7 % |
General
Short circuit proof | conditionally short-circuit proof |
Switching group | Iii0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 20 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Screw terminal |
Size and Weight
Width | 176 mm / 6.93 in |
Height | 176 mm / 6.93 in |
Depth | 283 mm / 11.14 in |
Weight | 9.1 kg / 20.06 lbs |
Low Voltage Directive | EN 61558-2-4 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |