Control- and isolating transformer
STE 800/4/23
Characteristics
General data
The control transformers of the STE series ensure safe galvanic isolation of the primary circuit from the secondary circuit. The unique BLOCK IMPEX vacuum impregnation process provides excellent protection against external influences while reducing noise levels. Installation is simple and quick thanks to the innovative push-in terminal technology.
Benefits
› Control and isolating transformer according to EN (IEC) 61558-2-2 and EN (IEC) 61558-2-4
› Very good inrush behavior due to reduced inrush currents
› High power density through a compact design concept
› Primary side ±5% taps for voltage adjustment
› Touch-protected connection terminals according to UVV BGV A3
Product | Control- and isolating transformer |
Order number | STE 800/4/23 |
Series | STE |
Power | 800 VA |
Input | 380 V / 400 V / 420 V |
Output | 230 V • 3.48 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 34.25 W |
No-Load Losses | 22.17 W |
Short-Term Power / instantaneous output | 3,400 VA |
Short circuit voltage uk | 3.3 % |
EN Insulation class | B (130°C) |
UL Insulation class | class 130 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 93.4 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Ii0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 1 |
Electrical Connections
Input terminal | Push-in terminal |
Output terminal | Push-in terminal |
Terminal PE | Flat plug connection |
Size and Weight
Width | 150 mm / 5.91 in |
Height | 143 mm / 5.63 in |
Depth | 130 mm / 5.12 in |
Weight | 10.5 kg / 23.149 lbs |
Low Voltage Directive |
EN 61558-2-2 EN 61558-2-4 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |