Toroidal transformers, safety isolating transformer

RTE 50/2x18 - Discontinued types - not for new designs

Characteristics

General data

The toroidal transformers of the RTE series enable space-saving use due to minimal size with maximum performance. The transformers feature overload protection thanks to the built-in thermal fuse and have a lightweight design. The connections can be soldered directly onto a PCB.

Benefits

 Safety isolating transformer according to EN (IEC) 61558-2-6

 Dual output coils for series or parallel connection

 Minimal no-load losses

 Excellent temperature behavior due to low magnetic stray field

 Very low noise field

Product Toroidal transformers, safety isolating transformer
Order number RTE 50/2x18
Series RTE
Power 50 VA
Input 230 V
Output 2 x 18 V • 1.39 Aac
Phases 1
Frequency range 50 Hz to 60 Hz
Short-Circuit Losses 9.8 W
No-Load Losses 0.4 W
Short circuit voltage uk 15.6 %
EN Insulation class B (130°C)
UL Insulation class class 105
Duty Cycle 100 %
Wire material Copper
Efficiency 83.1 %
General
Short circuit proof not short-circuit proof
Switching group Iii0
Cooling type AN
Environment
Ambient temperature -20 °C to 40 °C / -4 °F to 104 °F
Max. installation height 2,000 m / 6,562 ft
Protection and Safety
Protection type IP 00
Protection class (prepared) II
Overvoltage category III
Degree of contamination 2
Electrical Connections
Input terminal Stranded wire
Output terminal Wire connection
Size and Weight
Weight 0.68 kg / 1.499 lbs
Low Voltage Directive EN 61558-2-6
Approval cURus - Recognized UL 5085-1/-2; CSA 22.2

This could also be of interest to you

RTE 60/2x18
Toroidal transformers, safety isolating transformer • 1ph • 60 VA • IN: 230 Vac • OUT: 2 x 18 Vac
Product details
RTE 40/2x18
Toroidal transformers, safety isolating transformer • 1ph • 40 VA • IN: 230 Vac • OUT: 2 x 18 Vac
Product details
RTE 50/2x24
Toroidal transformers, isolating transformer • 1ph • 50 VA • IN: 230 Vac • OUT: 2 x 24 Vac
Product details
RKD 50/2x18
Toroidal transformers, safety isolating transformer • 1ph • 50 VA • IN: 2 x 115 Vac • OUT: 2 x 18 Vac
Product details
RKD 60/2x18
Toroidal transformers, safety isolating transformer • 1ph • 60 VA • IN: 2 x 115 Vac • OUT: 2 x 18 Vac
Product details
RKD 40/2x18
Toroidal transformers, safety isolating transformer • 1ph • 40 VA • IN: 2 x 115 Vac • OUT: 2 x 18 Vac
Product details