Toroidal transformers, isolating transformer
RKD 625/2x115
Characteristics
General data
The toroidal transformers of the RKD series enable space-saving use due to minimal size with maximum performance. The low magnetic stray field does not affect surrounding components and ensures excellent temperature behavior. The connections can be soldered directly onto a PCB.
Benefits
› Isolating transformer according to EN (IEC) 61558-2-4
› Lightweight
› Dual input and output coils for series or parallel connection
› Minimal no-load losses
› Very low noise field
Product | Toroidal transformers, isolating transformer |
Order number | RKD 625/2x115 |
Series | RKD |
Power | 625 VA |
Input | 2 x 115 V |
Output | 2 x 115 V • 2.7 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 25 W |
No-Load Losses | 4.2 W |
EN Insulation class | B (130°C) |
UL Insulation class | class 105 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 95.5 % |
General
Short circuit proof | not short-circuit proof |
Switching group | IIii0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | II |
Overvoltage category | III |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Stranded wire |
Output terminal | Wire connection |
Size and Weight
Width | 154 mm / 6.06 in |
Height | 74 mm / 2.91 in |
Depth | 154 mm / 6.06 in |
Weight | 6.1 kg / 13.448 lbs |
Low Voltage Directive | EN 61558-2-4 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |