Primary switched mode power supply, three-phase
PC-0324-200-0
Characteristics
Benefits
› Stabilised and adjustable output voltage
› Fast tripping of conventional circuit breakers
› DC OK signalling
› Parallel operation
› Push-in terminals
› Robust DIN rail mounting
› Resistant to transient overvoltages up to 4 kV
› 3 years warranty
Product | Primary switched mode power supply, three-phase |
Order number | PC-0324-200-0 |
Input
Rated input voltage | 400 Vac to 500 Vac |
Input voltage range | 320 Vac to 575 Vac |
Input voltage range | 450 Vdc to 800 Vdc |
Rated input current (rated load) (400Vac) | 1.21 A |
Rated input current (rated load) (500Vac) | 1.03 A |
Rated frequency range AC | 44 Hz to 66 Hz |
Rated frequency range DC | 0 Hz |
Inrush current limitation NTC < | 30 A |
Recommended preliminary fuse | 6A, 10A, 16A, B/C-Char. |
Mains failure bridging (rated load) (400Vac) | 15.0 ms |
Mains failure bridging (rated load) (500Vac) | 25.0 ms |
Output
Power | 480 W |
Rated output voltage | 24 Vdc |
Rated Output Current | 20 A |
Output voltage range | 23 Vdc to 28.5 Vdc |
Output Current Limitation (Constant Current) typ. | 22 A |
Ripple (rated load) typ. | 30 mVss |
Max. feedback resistance | 35 Vdc |
Verlustleistung Leerlauf (400Vac) | 4.03 W |
Verlustleistung Nennlast (400Vac) | 42.53 W |
Überspannungsschutz des Ausgangs | 40.0 Vdc |
Parallel connection possible | Yes |
Series connection possible | Yes |
Signaling
Signal output | Relay contact |
Status display | Green LED |
Environment
Ambient temperature | -25 °C to 70 °C / -13 °F to 158 °F |
Storage Temperature | -25 °C to 85 °C / -13 °F to 185 °F |
Humidity without condensation | 5 % to 96 % |
Cooling type | natural convection |
Required minimum distance (side) | 0 mm |
Required minimum distance (top/bottom) | 50 mm |
Protection and Safety
Degree of pollution | 2 |
Protection class according to EN 61140 | III, without PE connection |
Size and Weight
Width | 80 mm / 3.15 in |
Height | 127 mm / 5 in |
Depth | 160 mm / 6.3 in |
Weight | 1.51 kg / 3.33 lbs |
EMV-Richtlinie | EN 61204-3 |
Low Voltage Directive |
EN 61558-2-16 + A1 EN 60950-1 + A11 + A1 + A12 + AC + A2 |
RoHS compliant | EN IEC 63000 |