Line reactor, three-phase
LR3-AE100-404-0
Characteristics
Benefits
› Use as line reactor, commutating reactor or PFC reactor
› Ensuring the short-circuit voltage of 4 % to the mains
› Power harmonic damping
› Starting current limitation
› Increases the service life of consumers
› Low ripple
› Bridging voltage dips
› Peak current limitation
› Very good corrosion protection and low noise due to vacuum impregnation
› AD and AE types with UL approval
Product | Line reactor, three-phase |
Order number | LR3-AE100-404-0 |
Inductance | 3x 0.3 mH |
Rated current | 3x 100 Aac |
Linear current | 3x 150 Aac |
Rated voltage range | 0 V to 690 V |
Rated voltage | 400 V |
Phases | 3 |
Frequency range | 50 Hz to 60 Hz |
Short circuit voltage | 4% @ 400 V |
Motor or converter power | 55 kW / 73.76 HP |
EN insulation class | H (180°C) |
UL Insulation class | class 180 |
Duty Cycle | 100 % |
Power loss | 310.00 W |
Wire material | Aluminum |
General
Duty Cycle | 100 % |
Cooling type | AN |
Switching group | III0 |
Environment
Ambient temperature | -10 °C to 40 °C / 14 °F to 104 °F |
Max. installation height | 1,000 m / 3,281 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Bolt connection |
Output terminal | Bolt connection |
Terminal PE | Bolt connection |
Size and Weight
Width | 300 mm / 11.81 in |
Height | 198 mm / 7.8 in |
Depth | 168 mm / 6.61 in |
Weight | 17.6 kg / 38.8 lbs |
Low Voltage Directive | EN 61558-2-20 |
RoHS compliant | EN IEC 63000 |
Approval cULus - Listed | UL 508; CSA 22.2 |