Radio interference suppression filter, low leakage current

HLE 310-230/16

Characteristics

Benefits

 For enhanced requirements

 Low leakage current

 Single-stage filter concept

 Efficient filter effect against line-bound interference emissions

 Increase in the interference immunity of the connected consumer

Product Search
Product Radio interference suppression filter, low leakage current
Order number HLE 310-230/16
Series HLE 310
Inductance 6.5 mH
Rated current 16 Aac
Rated voltage range 0 V to 250 V
Rated voltage 230 V
Phases 1
Frequency range 50 Hz to 60 Hz
Motor or converter power 1.5 kW / 2.01 HP
EN insulation class A (105°C)
UL Insulation class class 105
Duty Cycle 100 %
Power loss 8.60 W
Wire material Copper
General
Duty Cycle 100 %
Cooling type AN
Environment
Ambient temperature -25 °C to 50 °C / -13 °F to 122 °F
Protection and Safety
Protection type IP 20
Protection class (prepared) I
Degree of contamination 2
Electrical Connections
Input terminal Screw terminal
Output terminal Screw terminal
Terminal PE Bolt connection
Size and Weight
Width 38 mm / 1.5 in
Height 190 mm / 7.48 in
Depth 75 mm / 2.95 in
Weight 0.78 kg / 1.72 lbs
RoHS compliant EN IEC 63000