Harmonic filter, three-phase
HFM-FB 100-400
Characteristics
Benefits
› Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers or controlled B6C thyristor bridges
› Compliance with EN 61000-3-2, EN 61000-3-12
› Support in the compliance with IEEE 519, D-A-CH-CZ
› Cos(phi) 0,95 at rated current
› Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
› Use of the HFM as a central sum filter for multiple converters possible
Product | Harmonic filter, three-phase |
Order number | HFM-FB 100-400 |
Inductance | 3x 0 mH |
Rated current | 3x 144 Aac |
Linear current | 3x 216 Aac |
Rated voltage range | 380 V to 420 V |
Rated voltage | 400 V |
Phases | 3 |
Frequency range | 50 Hz |
Motor or converter power | 75 kW / 100.58 HP |
EN insulation class | F (155°C) |
UL Insulation class | class 155 |
Duty Cycle | 100 % |
Power loss | 922.00 W |
General
Duty Cycle | 100 % |
Cooling type | AFAN |
Switching group | III0 |
Temperature monitoring | Bi-Metall Schalter |
Environment
Ambient temperature | -10 °C to 40 °C / 14 °F to 104 °F |
Max. installation height | 1,000 m / 3,281 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Bolt connection |
Output terminal | Bolt connection |
Terminal PE | Bolt connection |
Size and Weight
Width | 1060 mm / 41.73 in |
Height | 400 mm / 15.75 in |
Depth | 393 mm / 15.47 in |
Weight | 152 kg / 335.1 lbs |
Low Voltage Directive | EN 61558-2-20 |
Approval cURus - Recognized | UL 508; CSA 22.2 |