Autotransformer
ESP 400/1,6
Characteristics
Benefits
› Low weight and small size (compared to isolating transformers)
› Very high efficiency
› Very good moisture protection and low noise thanks to BLOCK IMPEX vacuum impregnation
› Contact protected screw connection terminals complying with UVV BGV A3
› Simple mounting thanks to robust metal footplate with oval slots
Product | Autotransformer |
Order number | ESP 400/1,6 |
Series | ESP |
Power | 496 VA |
Input | 400 V |
Output |
140 V • 1.6 Aac oder 170 V • 1.6 Aac oder 200 V • 1.6 Aac oder 235 V • 1.6 Aac oder 270 V • 1.6 Aac oder 310 V • 1.6 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 12 W |
No-Load Losses | 6 W |
EN insulation class | B (130°C) |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 96.5 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Ia0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Screw plug-in connection |
Size and Weight
Width | 85 mm / 3.35 in |
Height | 118 mm / 4.65 in |
Depth | 105 mm / 4.13 in |
Weight | 3.03 kg / 6.68 lbs |