Control transformer
BUST 6300/4/23
Characteristics
Benefits
› High power density due to a compact construction design
› Primary side ±5 % tappings for voltage adjustment
› Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation
› Contact protected screw connection terminals complying with UVV BGV A3
› Low height
Product | Control transformer |
Order number | BUST 6300/4/23 |
Power | 6,300 VA |
Input | 380 V / 400 V / 420 V |
Output | 2 x 115 V • 27.4 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 180 W |
No-Load Losses | 70 W |
Short-Term Power / instantaneous output | 16,000 VA |
Short circuit voltage uk | 2.6 % |
EN insulation class | B (130°C) |
UL Insulation class | class 130 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 96.2 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Iii0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 1 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Screw terminal |
Size and Weight
Width | 350 mm / 13.78 in |
Height | 220 mm / 8.66 in |
Depth | 280 mm / 11.02 in |
Weight | 58 kg / 127.87 lbs |
Low Voltage Directive | EN 61558-2-2 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |