Control transformer
BUST 5000/23/23
Characteristics
General data
The control transformers of the BUST series ensure safe galvanic isolation of the primary circuit from the secondary circuit. The unique BLOCK IMPEX vacuum impregnation process provides excellent protection against external influences while reducing noise levels. The transformers feature a low profile design.
Benefits
› Control transformer according to EN (IEC) 61558-2-2
› High power density through a compact design concept
› Primary side ±5% taps for voltage adjustment
› Very good inrush behavior due to reduced inrush currents
› Horizontal design
› Touch-protected connection terminals according to UVV BGV A3
Product | Control transformer |
Order number | BUST 5000/23/23 |
Series | BUST |
Power | 5,000 VA |
Input | 219 V / 230 V / 241 V |
Output | 2 x 115 V • 21.7 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 150 W |
No-Load Losses | 70 W |
Short-Term Power / instantaneous output | 15,700 VA |
Short circuit voltage uk | 2.9 % |
EN Insulation class | B (130°C) |
UL Insulation class | class 130 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 95.8 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Iii0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 1 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Screw terminal |
Size and Weight
Width | 325 mm / 12.8 in |
Height | 190 mm / 7.48 in |
Depth | 240 mm / 9.45 in |
Weight | 42.5 kg / 93.696 lbs |
Low Voltage Directive | EN 61558-2-2 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |